Change language

Ezi-IO Ethernet AD

Analog input module for Ethernet: acquires the measured values of pressure, temperature, level or distance sensors directly at the machine and makes them available to your application over the network – without long, noise-prone analog lines to the control cabinet.

Design and function
Eight channels in one module measure either voltage (up to ±10 V) or current (0–20 mA). Input mode and range are set per channel, so different sensors can work on a single module. A moving average filter smooths noisy signals before they reach your application. All eight channels are converted within 200 µs – so even fast signal changes are captured. Wiring is via a terminal block, mounting on a DIN rail.

Ethernet communication
The module connects to a standard Ethernet network (UDP/TCP) and is addressed directly from your own PC application – no fieldbus master required. An I/O library (API) for Windows and Linux is provided for this; a Windows user program helps with commissioning and testing.

Ezi-IO Ethernet AD
Produktfilter
In stock only  

Choose a frame size to see matching products.

Zubehör

RJ45 cable
CGNR-EC-001F
1 m · Standard€12,40
CGNR-EC-002F
2 m · Standard€15,40
CGNR-EC-003F
3 m · Standard€20,00
CGNR-EC-005F
5 m · Standard€29,20