Change language

Analog I/O module

Ezi-IO-CT-DA04-T

Price on request

Product inquiry

Contact details

Product details

Item no. – Product name Ezi-IO-CT-DA04-T

Drawings or files? Simply reply to our response email with the attachment.

Produktbeschreibung

Analog output module for CC-Link IE TSN: outputs the controller's setpoints as voltage or current – for proportional valves, frequency inverters or controllers, for example – and sits right next to the device it drives.

Design and function
Four channels deliver either voltage (0–5 V, 1–5 V, 0–10 V, ±10 V) or current (0–20 mA, 4–20 mA); the range is selected per channel. A resolution of 1/50,000 allows setpoints to be graded finely. The calibration function compensates for output deviation, so the device receives exactly what the controller specifies. Wiring is via a terminal block, mounting on a DIN rail.

CC-Link IE TSN communication
The module is integrated into CC-Link IE TSN networks as a class B station and operates asynchronously or cycle-synchronously, depending on the application. Two RJ45 ports allow daisy-chaining from module to module, with up to 100 m between stations.

Technische Spezifikationen

I/O module Ezi-IO-CT-DA04-T

Supply voltage
24 V DC ±10 %
Current consumption
180 mA
Connection method
Terminal block
Protocol
CC-Link IE TSN, Authentication Class B
Synchronization
Asynchronous, synchronous mode
Bus interface
2 × RJ45
Cable
STP (shielded twisted pair), Cat. 5e or higher, max. 100 m
LED display
Power status (PWR), CC-Link IE TSN status (RUN), Operation error (ERR), CC-Link IE TSN connection (P1, P2)
Ambient temperature (in use)
0 … 50 °C
Ambient temperature (storage)
-20 … 70 °C
Humidity in use (non-condensing)
35 … 85 %
Humidity in storage (non-condensing)
10 … 90 %
Vibration resistance
0.5 g

Analog output (voltage) Ezi-IO-CT-DA04 – Voltage Output

Number of channels
4
Signal range
0 … 5 V, 1 … 5 V, 0 … 10 V, −10 … 10 V
Range setting method
Parameter setting window (per channel CH1–CH4), DIP switch (per channel CH1–CH4)
External load resistance
≥ 1 kΩ
Max. resolution
1/50,000 (full scale)
Accuracy at 25 °C
±0.3 % (full scale)
Accuracy at 0–50 °C
±0.4 % (full scale)
Conversion cycle
500 µs (for 4 channels)
A/D converted data
−10 … 10 V: −25,000 … 25,000, Other ranges: 0 … 25,000
Isolation
Digital isolation between analog output and CC-Link IE TSN connectors (channels not isolated from each other)

Analog output (current) Ezi-IO-CT-DA04 – Current Output

Number of channels
4
Signal range
0 … 20 mA, 4 … 20 mA
Range setting method
Parameter setting window (per channel CH1–CH4), DIP switch (per channel CH1–CH4)
External load resistance
≤ 400 Ω
Max. resolution
1/50,000 (full scale)
Accuracy at 25 °C
±0.3 % (full scale)
Accuracy at 0–50 °C
±0.4 % (full scale)
Conversion cycle
500 µs (for 4 channels)
A/D converted data
0 … 25,000
Isolation
Digital isolation between analog output and CC-Link IE TSN connectors (channels not isolated from each other)